Description
- The switch mainly consists of two major parts: a steel plate base and a plastic upper cover. Three pairs of clip-type contacts and arc chambers are mounted on the base through insulating pads, while the fuse links are installed in the upper cover and directly function as moving contact blades. The upper cover can rotate along the hinge pin in a fan-shaped motion, allowing the fuse links to be completely withdrawn from the socket. The upper cover can also be easily removed from the base, facilitating switch installation and safe fuse replacement.
- The arc chamber is made of arc-resistant molded plastic, featuring a simple structure, convenient assembly and disassembly, as well as safe and reliable operation. Multiple metal arc extinguishing plates are installed inside the chamber to enhance arc extinguishing performance, eliminate arc hazards, and extend the service life of the contacts.
- The switch is equipped with a spring energy storage quick-closing mechanism, enabling fast, safe, and reliable making and breaking operations.
- An auxiliary contact can be installed on the left side of the switch and used together with fuse links equipped with a fuse striker. When a fuse link on any phase blows and the striker is released, the transmission shaft actuates the auxiliary contact to generate a signal, which can be used for phase-loss detection and protection purposes.
Scope of Application
The HR5 Series Fuse-Switch Disconnector (hereinafter referred to as the “switch”) is suitable for AC 50Hz power systems with rated voltage up to 660V and conventional thermal current up to 630A. It is designed for distribution circuits and motor circuits with high short-circuit current levels.
It is used as a manually operated, infrequent switching device for power supply control, isolation, and emergency switching, and also provides short-circuit protection for electrical circuits. However, it is generally not intended for direct switching of individual motors.
The switch features a simple structure and convenient operation, and complies with IEC 60947-3 and GB/T 14048.3 standards. It is an ideal choice among similar products in this category.
Model and Meaning

Main Technical Specifications
1. Main Technical Parameters of the Switch
| Switch Model | HR5-100 | HR5-200 | HR5-400 | HR5-630 | |
| Rated Insulation Voltage Ui | 690V | ||||
| Rated Frequency | 50Hz | ||||
| Rated Operational Voltage Ue | AC 380, 660V | ||||
| Conventional Thermal Current Ith | 100A | 200A | 400A | 630A | |
| Rated Operational Current Ie | 400V/AC-23B | 100A | 200A | 400A | 630A |
| 660V/AC-22B | 100A | 200A | 315A | 425A | |
| Rated Making Capacity (400V/AC-23) rms | 1000A | 2000A | 3200A | 5040A | |
| Rated Breaking Capacity (400V/AC-23) rms | 800A | 1600A | 2400A | 3780A | |
| Rated Conditional Short-Circuit Current (r.m.s) | 50kA | 50kA | 50kA | 50kA | |
| Mechanical Life (Operating Cycles) | 3000 | 3000 | 1500 | 1500 | |
| Electrical Life (Making/Breaking Cycles) | 600 | 600 | 300 | 300 | |
| Operating Force F | ≤ 250N | ≤ 300N | ≤ 350N | ≤ 400N | |
| Weight | 2.95kg | 6.4kg | 8.1kg | 9.9kg | |
2. Main Parameters of Auxiliary Contacts (LX19K Limit Switch)
a. Rated operational voltage: AC 400V
b. Rated thermal current: 5A
c. Utilization category: AC-15
d. Contact configuration: 1NO + 1NC (one normally open and one normally closed)
e. Standard compliance: GB/T 14048.5
3. Matching Relationship Between the Switch and Fuse Links
Conventional Thermal Current Ith | Rated Operational Voltage Ue | Fuse-link Size | Rated Current of Fuse-link (A) |
100A | 380V | NT00 | 4, 6, 10, 16, 25, 32, 40, 50, 63, 80, 100, 125, 160 |
660V | NT00 | 4, 6, 10, 16, 25, 32, 40, 50, 63, 80, 100 | |
200A | 380V | NT1 | 80, 100, 125, 160, 200, 225, 250 |
660V | NT1 | 80, 100, 125, 160, 200 | |
400A | 380V | NT2 | 125, 160, 200, 225, 250, 300, 315, 355, 400 |
660V | NT2 | 125, 160, 200, 225, 250, 300, 315 | |
630A | 380V | NT3 | 315, 355, 400, 425, 500, 630 |
660V | NT3 | 315, 355, 400, 425 | |
Note: When the switch is used in motor circuits, the rated current of the fuse-link is allowed to be greater than the rated operational current of the switch. | |||
Switch shape and installation dimensions
HR5-100 Fuse-type Disconnector Switch

HR5-200.400.630 Fuse-type Disconnector Switch

Product Model | Outline Dimensions (mm) | Installation Dimensions (mm) | Terminal Dimensions | ||||||||
A | B | C | D | E | F | a | b | Φc | Cross Section | M | |
HR5-100/30 | 150 | 225 | 130 | 40 | 245 | 270 | 132 | 21 | 7 | 1.5×20 | M8 |
HR5-100/31 | 160 | 225 | 130 | 40 | 245 | 270 | 132 | 21 | 7 | ||
HR5-200/30 | 203 | 264 | 193 | 62 | 280 | 342 | 130 | 60 | 9 | 4×25 | M10 |
HR5-200/31 | 220 | 264 | 193 | 62 | 280 | 342 | 130 | 60 | 9 | ||
HR5-400/30 | 226 | 264 | 210 | 70 | 280 | 358 | 130 | 60 | 9 | 5×25 | M12 |
HR5-400/31 | 242 | 264 | 210 | 70 | 280 | 358 | 130 | 60 | 9 | ||
HR5-630/30 | 272 | 264 | 224 | 85 | 280 | 372 | 200 | 60 | 9 | 6×30 | M12 |