Build your earth-leakage protection specification around the load. Compare residual-current types, define the sensitivity and pole arrangement, and check the overcurrent coordination your distribution system needs.

Match the residual-current response to the connected equipment.
Specify IΔn separately from the continuous-current rating.
Provide suitable overload and short-circuit protection.
A residual current circuit breaker detects an imbalance between currents in the monitored live conductors and disconnects under its declared residual-current conditions. It provides residual-current protection without integral overload or short-circuit protection.
An RCCB helps reduce risks associated with current leaving the intended circuit path. Its protection depends on the selected type, sensitivity, installation and correct coordination.
An RCCB does not replace an MCB or fuse. Your design needs suitable overcurrent protection for the circuit and the RCCB itself.
A current rating alone cannot define a suitable device. Record waveform response, IΔn, supply, poles and the required supporting documents together.
Use the expected residual-current waveform to choose a category. The following cards explain selection principles; they do not declare the availability or certification of a particular Bddkg model.
Responds to sinusoidal AC residual currents. Use only where the connected load and applicable installation rules allow this response.
Responds to sinusoidal AC and specified pulsating DC residual currents. Check electronic equipment requirements and any need for additional DC detection.
Adds response to specified composite residual currents associated with suitable single-phase inverter equipment. Confirm the equipment instructions and device operating range.
Adds detection of smooth DC and other specified residual-current components. Confirm frequency response and application limits for the exact model.
Shortlist a response category first, then verify the complete rating combination. These editable comparison rows describe technical categories rather than a supplier model catalogue.
AC / A / F / B
Subject to the declared operating conditions and installation rules.
A / F / B
Check the equipment specification; Type AC is not the route for this waveform.
F or application-specific B
Confirm frequency components and the manufacturer’s equipment requirements.
B within its declared range
Type A or F alone does not provide Type B smooth-DC detection.
Model-specific characteristics
Immunity to disturbances and selectivity are separate checks from waveform type.
Rated current In and rated residual operating current IΔn answer different questions. Keep them in separate fields on your schedule so engineering and purchasing teams approve the same device.
This identifies the current the RCCB is rated to carry under declared conditions. It is not an overload trip setting; coordinate the load and overcurrent protection accordingly.
This defines the rated residual-current sensitivity. Your protection objective, normal leakage, disconnection requirements and applicable rules determine the appropriate choice.
For example, “63 A / 30 mA” describes two independent ratings: 63 A is the rated current and 30 mA is IΔn. This is a terminology example, not an advertised Bddkg configuration. A higher ampere rating does not mean a higher leakage threshold.
Do not choose an RCCB threshold from price or nuisance-tripping history alone. Identify the intended protective function and establish whether a general or time-delayed device is appropriate.
Often associated with additional personal protection where required. The installation design and local rules determine the permitted value and conditions of use.
May be used for other protective objectives where permitted. These values are not substitutes for 30 mA additional personal protection where that is required.
An upstream device may need a suitable delay and sensitivity relationship. Confirm coordination from technical data; different thresholds alone do not guarantee discrimination.
Define the actual conductor arrangement before comparing device dimensions. Check the internal test circuit and connection instructions as carefully as the pole marking.
A 2-pole arrangement is a common starting point where phase and neutral must be monitored and switched. Confirm the exact supply, terminals and local requirements.
A 4-pole arrangement is a common route for three-phase circuits with neutral. Neutral-free applications require explicit confirmation of permitted connections and test operation.
Verify width, depth, busbar system, conductor capacity, tightening torque and enclosure conditions. Shared DIN-rail mounting does not establish electrical interchangeability.
Application names are useful conversation starters. Equipment instructions and possible residual-current components determine the response your installation needs.
Review appliances and the circuit grouping before selecting a type. A shared RCCB can disconnect multiple downstream circuits, so consider the impact of an outage.
Electronic lighting, office equipment and power supplies can contribute normal leakage. Assess the combined load and protective arrangement instead of selecting from a building label.
Obtain the equipment maker’s protective-device requirements. Inverter topology and possible DC components determine whether a Type F or Type B route is appropriate.
Check charger DC detection and the instructions for PV, storage or UPS equipment. Type B detection does not by itself establish suitability for a DC power circuit.
An EV charging circuit needs a coordinated protective arrangement. Do not assume every charger has the same integrated detection or that any Type A RCCB can be used without further checks.
Identify any integrated 6 mA DC residual-current detection, its declared standard and the upstream device required by the charger manufacturer.
Where permitted, suitable additional DC detection may support a Type A arrangement; other applications may require Type B. Verify the complete solution against applicable rules.
Follow the same sequence for each configuration so your shortlist can be reviewed consistently.
Record voltage, frequency, phases, neutral arrangement and destination market. Include the equipment instructions and any project-specific protective requirements.
Consider AC, pulsating DC, composite and smooth DC components. Select a response category that matches the load rather than assuming Type AC suits all circuits.
Confirm rated current, IΔn, normal leakage and the protection objective. Review ambient derating and the number of circuits sharing the device.
Identify the MCB, fuse or other overcurrent protection. Verify the RCCB’s conditional short-circuit rating with the declared backup device and installation fault level.
Approve poles, dimensions, connection instructions, test operation and required documents for the ordered configuration. Resolve any missing details before accepting a substitute.
Residual-current operation and short-circuit withstand are different characteristics. A conditional short-circuit rating is not a declaration that an RCCB provides standalone overcurrent interruption.
Check the permitted loading and the protective arrangement for the RCCB. Do not assume the sum of downstream breaker ratings automatically establishes adequate protection.
Use the specified backup device and manufacturer coordination data. Check the rated conditional short-circuit current at the relevant voltage and prospective fault level.
Review sensitivity, delay and the time/current relationship of upstream and downstream RCDs. Reliable discrimination needs evidence for the proposed arrangement.
Choose the protective functions and circuit grouping your project needs. Compare the complete arrangement, including service continuity and maintenance.
Separates residual-current protection from the overload and short-circuit functions. Review how many circuits share the RCCB and the consequences of one trip.
Combines residual-current and overcurrent functions in one device. Circuit-level arrangements can reduce the extent of an outage when properly coordinated.
Provides overcurrent protection within its declared characteristics. An ordinary MCB does not detect residual current or replace an RCCB where that function is needed.
Use qualified installation personnel, the exact product instructions and applicable installation rules. A category guide cannot establish a wiring arrangement for a particular board.
Check permitted supply direction, neutral connections, conductor preparation and torque. Incorrectly shared neutrals or unintended neutral-to-earth connections can cause problems that a device change will not solve.
Carry out the required commissioning checks. The built-in test button checks a device function; it does not prove earthing integrity or replace the installation verification process.
Assess faults, moisture, normal leakage and disturbances before considering a different device. Follow the specified test interval and maintenance instructions rather than repeatedly resetting without investigation.
Treat standards, declarations, test reports and certificates as different evidence. Match each document to the exact product, rating combination and destination market.
Ask for response type, In, IΔn, voltage, frequency, poles, time characteristics, conditional ratings, dimensions and environmental limitations.
Verify wiring arrangements, test procedure, terminal capacity, torque, permitted supply direction and any required backup protective device.
Check issuer, report or certificate number, covered models, standard edition and market scope. A standard reference alone does not establish third-party certification.
IEC 61008-1:2024 covers household and similar-use RCCBs without integral overcurrent protection. IEC 62423 addresses additional Type F and Type B requirements. Confirm national adoptions and the editions required for your project; these references do not certify any Bddkg model.
Send one rating schedule for each configuration. A complete brief helps your supplier identify missing technical details before a sample or commercial offer is reviewed.
Supply voltage and frequency; current; poles; residual-current type; sensitivity; delay; normal leakage; fault level and the proposed overcurrent protection.
Connected equipment, operating environment, board arrangement, destination country, specified standards and the documents your approval process requires.
Quantity by configuration, delivery destination, sample needs and requested marking or packaging. Confirm availability and any customization with the proposed model.
Use the relevant reference for the question you are resolving, then return to the exact device documentation before approval.
Review the relationship between residual-current devices, RCCBs and RCBOs before preparing a specification.
Read the official scope of IEC 62423 for the additional requirements applicable to these residual-current types.
Bring your circuit schedule and equipment instructions to the enquiry so model selection starts from actual conditions.
Practical answers for your initial technical and purchasing review.
RCCB means residual current operated circuit-breaker without integral overcurrent protection. It detects specified residual-current conditions and disconnects the circuit within its declared characteristics.
No. Provide suitable overcurrent protection and verify coordination for the exact RCCB, backup device, operating voltage and prospective fault current.
An RCCB provides residual-current protection without integral overcurrent protection. An RCBO combines residual-current and overcurrent functions; both require correct selection for the installation.
No. It is a rated-current value. Residual sensitivity is recorded separately as IΔn, typically expressed in milliamperes on a product schedule.
Start with equipment instructions and the residual-current waveforms that can occur. Confirm the declared device response and applicable installation requirements.
Type A addresses specified AC and pulsating DC residual currents. Do not use it as a substitute for Type B where smooth DC detection is required.
No. Type F covers specified composite waveforms associated with suitable single-phase equipment. Some applications require Type B or another arrangement stated by the equipment manufacturer.
A Type B residual-current classification describes detection behavior. Suitability for switching a DC power circuit requires explicit voltage and switching ratings for that circuit.
Not where 30 mA additional personal protection is required. Select sensitivity for the intended protection objective and applicable rules rather than treating higher thresholds as interchangeable.
The permitted arrangement depends on the charger’s integrated DC detection, manufacturer instructions and installation rules. Confirm the complete protective arrangement rather than selecting from the application name.
Only where the product instructions permit the proposed connection and the internal test circuit operates correctly. Do not infer suitability from the pole count alone.
It describes performance under specified conditions with a declared protective arrangement. Check the backup device and documentation; the rating does not give an RCCB integral overcurrent protection.
No. Sensitivity and time characteristics must be coordinated using the relevant technical data. A larger upstream ampere rating alone does not establish residual-current discrimination.
Possible causes include faults, moisture, accumulated normal leakage, wiring errors or disturbances. Arrange a competent investigation instead of repeatedly resetting or increasing the threshold without review.
No. Follow the manufacturer’s test instructions and complete the required installation verification. The button alone does not demonstrate earthing quality or the overall protective performance.
Provide application, supply, current, poles, residual-current type, IΔn, delay, upstream protection, fault level, quantity, destination and required documents. Confirm the exact offered configuration before ordering.
Share a complete circuit specification and the documents your project needs. Confirm the offered model, availability, ratings and supporting evidence before approving a sample or placing an order.
Include your equipment manual or circuit schedule where a particular protective arrangement is specified. Keep the requested type and sensitivity separate from the current rating.
Final design, installation and verification require qualified professional review and the exact device instructions.